Model: E4 LCD PRO 1000 Standard Version

 

An advanced technology
Equipped with the On Line Double Conversion controlled by a microprocessor, the E4 LCD Evolution range delivers a perfect sinewave output current and provides thorough and effective protection of critical devices.
The output power factor is optimal, reaching 0.9, to provide high performance and efficiency for critical applications.

 

Smart features

• Cold start function: It enables an emergency situation involving a total power cut to be overcome by starting the UPS using batteries without the mains power supply.

• UPS controlled by a microprocessor: Among other advantages this control mode provides a wide range of input voltage (110 V to 300 V), an input power ratio of more than 95 %, little harmonic distortion and effective noise reduction.

• Energy saving ECO mode (1 to 3kVA versions): Efficiency of up to 97 % equates to energy and cost savings. In addition, a static bypass power supply via the UPS offers timely return to on-line double conversion if required.

• Emergency Power Off (EPO): This function ensures the safety of personnel and hardware in the event of fire or Networks & critical applications - Industrial Environments From 1 to 10k VA any other emergency situation by triggering the total and immediate shutdown of the UPS.

 

Practical design
UPS status is seen at a glance on an intuitive LCD screen. The UPS is controlled by a simple control panel on the front with 3 or 4 buttons: ON/OFF, operating mode configuration, voltage setting, programmable outlet setting…

 

Communication
USB or RS 232 communication ports and SNMP interface enable an E4 LCD UPS to communicate with the various stations and IT servers it is protecting. The multiple communications function should be noted: USB or RS232 ports can therefore operate simultaneously with the SNMP interface.

 

Features

GENERAL CHARACTERISTICS

  • Technology On Line Double Conversion
  • Power (VA) 10000VA
  • Power (W) 9000 W
  • Power factor 0,9

PHYSICAL CHARACTERISTICS

  • Standard:
      • Dim. DxWxH: 442X190X688mm
      • Net weight: 82 kg

TECHNICAL INPUT CHARACTERISTICS

 

  • Low voltage range:
    • Low Line transfer (based on load percentage : 100%-80% / 80%-70% / 70%-60% / 60%-0%):
      • 110 VAC: +/- 3% at 50% load
      • 176 VAC: +/- 3% at 100% load
    • Low Line comeback:
      • 120 VAC +/- 3% at 50% load
      • 186 VAC +/- 3% at 100% load
  • High voltage range:
    • High Line transfer: (based on load percentage : 100%-80% / 80%- 70% / 70%-60% / 60%-0%) :
      • 300 VAC +/- 3%
    • High Line comeback:
      • 290 VAC +/- 3%
  • Frequency range
      • 50 Hz : 46 Hz ~ 64 Hz
      • Power factor > 0,99 at 100% load

TECHNICAL OUTPUT CHARACTERISTICS

  • Voltage:  208 / 220 / 230 / 240 VAC
  • AC voltage regulation (Batt mode): +/- 1%
  • Frequency range (Synchronized range): 50 Hz : 50 Hz : 46 Hz ~ 54 Hz or 60 Hz : 56 Hz ~ 64 Hz
  • Frequency range (Batt mode): 50 Hz +/- 0,1 Hz or 60 Hz +/- 0,1 Hz
  • Current crest ration: 3:1 (max)
  • Harmonic distorsion: <= 3% THD (Linear Load); <= 6% THD (Non-linear Load)
  • Transfer time: Line mode to battery mode 0 ms Inverter to Bypass: 0 ms
  • Waveform: Pure sinewave
  • Output outlets IEC standards: 0
  • Output terminal block: no

EFFICIENCY

  • AC mode: 90%
  • Battery mode: 89%

BATTERY

  • Standard model:
      • Battery type: 12 V / 9 AH
      • Number: 20
      • Typical recharge time: 9 hours recover to 90% capacity
      • Charging current: 1A (max 2A)
      • Backup time: from 5 to 30 minutes depending on the connected load

DISPLAY

  • LCD screen:  Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator.

AUDIBLE ALARMS

  • Battery mode: Sounding every 4 seconds
  • Low battery: Sounding every second
  • Overload: Sounding twice every second
  • Fault: Continuously sounding

MANAGEMENT / COMMUNICATION

  • Communication: USB & RS232 port and Infopower included software (support Windows family, Linux, Unix and MAC)

ENVIRONMENT

  • Humidity: 0 - 95% relative humidity @ 0-40° non condensing
  • Operating Altitude: Up to 1000 m above sea level (> 1000 m 1% deterioration for every 100 m)
  • Noise level: Less than 58dBA @ 1meter
  • Heat dissipation: max - HV (230 V) 960 W / 3276,45 Btu/h

NORMS

  • Standard: CE RoHS, cTUVus
  • EMC (Electromagnetic compatibility): EN 62040-2 : 2006 ; EN 61000-2-2 : 2002; EN61000- 4-2 : 2009; EN61000-4-3:2006 +A1:2008 +A2:2010; EN61000-4-4:2004+A1:2010; EN61000-4-5:2006; EN61000-4-8:2010
  • Low voltage (Safety): EN62040-1 : 2008