Model: INFOSECÂ E7 One 1500 RT
Unparalleled protection
Equipped with Online Double Conversion technology, E7 One RT range delivers perfect sinusoidal current to your
telecommunications equipment or other sensitive industrial applications. It guarantees total protection for connected
equipment against excess loads, surges and short circuits.
A battery connector on the rear panel allows the addition of backup modules dedicated to extending the
backup time that must be available to the equipment to be protected. On the front side, a battery status display
is available on the UPS screen.
The versatile rack/tower design of the E7 One RT makes it easy to use. It allows instantaneous integration and
is available in a wide variety of environments: horizontally in "rack position", in a 19'' bay server thanks to the
rackmount brackets (included), or vertically in the "tower" position thanks to its floor standing system (included).
Essential features
• Hot-swappable batteries to avoid interrupting the supply of critical and essential loads during maintenance
work
• Visual alarms and ring tones to warn in case of problems
• Cold start function for troubleshooting in case of power outage
• Automatic UPS restart when power is restored for quick restart
• Up to 3 UPSs can be connected in redundant parallel mode (N+X) in order
to have a capacity of 30kVA (optional from 6kVA models).
Specifications
GENERAL CHARACTERISTICS
- Technology:Â On Line Double Conversion
- Power:Â 1,500VA 1,500W
DIMENSION & WEIGHT
- Dimension L/D x W x H (mm): 410 x 438 x 88 (2U)
- Weight:Â 15.5 KgÂ
INPUT
- Rated voltage:Â 100/110/115/120/127VAC (LV) / 200/208/220/230/240VAC (HV)
- Voltage range: 55-150VAC ± 5% @ 50% load/80-150VAC ± 5% @ 100% load (LV)
- 110-300VAC ± 5% @ 50% load/160-300VAC ± 5% @ 100% load (HV)
- Frequency range: 40Hz ~ 70Hz
- Power Factor:Â >= 0.99 @ rated voltage (100% load)
- Harmonic distortion:Â <=5% @ rated input voltage
OUTPUT
- Voltage:Â 100*/110*/115*/120/127VAC (LV) or 200*/208*/220/230/240VAC (HV)
- Voltage control (battery mode): ± 1%
- Frequency range (synchronized range):Â Â 57 ~ 63Hz or 47 ~ 53Hz
- Frequency range (battery mode): 60Hz ± 0.1Hz or 50Hz ± 0.1Hz
- Crest factor:Â 3:1 (max.)
- Harmonic distortion:Â <=2% THD (Linear load) <=4% THD (Non linear load)
- Transfer time:
- Mains mode or battery mode: ZERO
- Bypass UPS:Â 4ms (Typical)
- Waveform:Â Pure sinusoidal
- Standard/programmable IEC output outlets:Â 4 (10A) + 4 (10A)
EFFICIENCY
- Mains Mode:Â >= 89% @ full battery charge
- Battery mode:Â >=96% @ full battery charge
- Eco mode:Â >= 88%
BATTERY
- Rated voltage: 41.1VDC ± 1%
- Recharge time:Â 3 hours at 95% capacity for batteries @ 2A charge current
- Charge current (max):Â 12A
- Cold start-up:Â Yes
- Backup time:Â 5 to 30 minutes depending on the connected load
BYPASS
- Static bypass:Â Yes
- Manual bypass: OptionÂ
INDICATORS & ALARMS
- LCD Screen:Â Charge level, battery level, mains mode, battery mode, bypass mode, fault indicator.
- Sound alarms:Â Battery mode, low battery, excess load, fault
MANAGEMENT / COMMUNICATION
- Communication:Â USB and RS232 port & Infopower software included (Windows family, Linux, Unix and MAC compatible)
- SNMP: Option: power management from SNMP (VMware® compatible, Hyper VTM) and Internet browser
- Parallel connector:Â Option
- EPO/CPAU connector:Â Yes
ENVIRONMENT
- Ideal environment: 20 to 90% relative humidity @ 0-40°C without condensation
- Noise level:Â less than 50dBA at 1 metre
- Altitude of operation:Â < 1,000m at rated power (> 1,000m 1% downgrade every 100m - max 4km)
- Max heat dissipation:Â 150W/511.5BTU/h
STANDARDS
- Standards:Â Â CE, RoHSÂ
- EMC (electromagnetic compatibility):Â EN62040-2: 2006+AC: 2006
- Low voltage (safety):Â EN62040-1:2008+A1:2013