Model: OEMÂ LPS333
Features
- Universal AC input voltage range
- Power will not de-rate for the entire input voltage range
- Power Boost of 150% for 5 seconds and 200% for 2 seconds
- Full corrosion resistant aluminium casing
- Conforms to harmonic current IEC/EN 61000-3-2, Class A
- Extreme low temperature cold start at -40°C
- Conformal coating on PCBAs to protect against common dust and chemical pollutants
- Hazardous Locations approval to ATEX and Class I, Div 2 (DRP048V480W1BA)
- Certified according to IEC/EN/UL 62368-1
Specifications
Input Ratings / Characteristics
- Nominal Input Voltage: 100-240Vac
- Input Voltage Range: 85-264Vac
- Nominal Input Frequency: 50-60Hz
- Input Frequency Range: 47-63Hz
- DC Input Voltage Range*: 120-375Vdc
- Input Current: < 5.00A @ 115Vac, < 3.00A @ 230Vac
- Efficiency at 100% Load: > 91.0% @ 115Vac, > 93.0% @ 230Vac
- Max Power Dissipation:
- 0% load < 5W @ 115Vac & 230Vac
- 100% load < 46.5W @ 115Vac, < 34.5W @ 230Vac
- Max Inrush Current: < 35A @ 115Vac & 230Vac
- Power Factor at 100% Load: > 0.96 @ 115Vac, > 0.90 @ 230Vac
- Leakage Current: < 3mA @ 240Vac
*Fulfills test conditions for DC input. Safety approval for DC input can be obtained upon request.
Output Ratings / Characteristics**
- Nominal Output Voltage: 48Vdc
- Factory Set Point Tolerance: 48Vdc ± 1%
- Output Voltage Adjustment Range: 48-56Vdc
- Output Current:
- 10.0A (continuously operating at 48V)
- 15.0A (Power Boost for 5 seconds at 48V, refer to the details in the Functions section)
- Output Power:
- 480W (continuously operating at 48V)
- 720W (Power Boost for 5 seconds at 48V, refer to the details in the Functions section)
- Line Regulation: < 0.5% (@ 85-264Vac input, 100% load)
- Load Regulation: < 1.0% (@ 85-264Vac input, 0-100% load)
- PARD*** (20MHz): < 200mVpp
- Rise Time: < 350ms @ nominal input (100% load)
- Start-up Time: < 1,500ms @ nominal input (100% load)
- Hold-up Time: > 20ms @ 115Vac & 230Vac (100% load)
- Dynamic Response (Overshoot & Undershoot O/P Voltage):
- ± 2% @ 85-264Vac input, 10-90% load
- (Slew Rate: 0.1A/?s, 50% duty cycle @ 5Hz to 1KHz)
- Start-up with Capacitive Loads: 10,000µF Max
**For power de-rating from > 50°C to 75°C, see power de-rating on page 3.
*** PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1?F ceramic capacitor & 47?F electrolytic capacitor.
Mechanical
- Case Cover / Chassis: Aluminium
Dimensions (L x W x D): 121 x 144 x 118.6 mm (4.76 x 5.67 x 4.67 inch)
- Unit Weight: 1.37 kg (3.02 lb)
- Indicator: Green LED: DC OK
- Cooling System: Convection
- Terminal:
- Input 3 Pins (Rated 300V/30A)
- Output 4 Pins (Rated 300V/30A)
- Wire:
- Input AWG 18-10
- Output AWG 16-10
- Mounting Rail: Standard TS35 DIN Rail in accordance with EN 60715
- Noise (1 Meter from power supply): Sound Pressure Level (SPL) < 25dBA
Environment
- Surrounding Air Temperature:
- Operating -25°C to +75°C (Cold Start at -40°C)
- Storage: -40°C to +85°C
- Power De-rating Temperature:
- > 50°C de-rate power by 2.5% / °C,
- > 70°C de-rate power by 5% / °C
- Operating Humidity: 5 to 95% RH (Non-Condensing)
- Operating Altitude: 0 to 2,500 Meters (8,200 ft.)
- Shock Test: Non-Operating: IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
- Vibration Non-Operating: IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction
- Bump Test: Operating: IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
- Over Voltage Category: III According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
- Pollution Degree: 2
Protections
- Overvoltage:
- < 57V, SELV Output, Hiccup Mode,
- Non-Latching (Auto-Recovery)
- Overload / Overcurrent:
- > 150% of rated load current, Hiccup Mode,
- Non-Latching (Auto-Recovery)
- Over Temperature:
- < 80°C Surrounding Air Temperature @ 100% load,
- Non-Latching (Auto-Recovery)
- Short Circuit: Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
- Transient Surge Voltage Protection: MOV (Metal Oxide Varistor)
- Internal Fuse at L pin: T8AH
- Degree of Protection: IP20
- Protection Against Shock: Class I with PE* connection
*PE: Primary Earth
Reliability Data
- MTBF:
- > 500,000 hrs. as per Telcordia SR-332
- I/P: 115Vac, O/P: 100% load, Ta: 25°C
- Expected Cap Life Time: 10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety Standards / Directives
- Electrical Equipment of Machines: EN 60204-1 (over voltage category III)
- Electrical Equipment for Use in Electrical Power Installations: IEC/EN 62477-1 / IEC 62103
- Safety Entry Low Voltage: PELV* (EN 60204-1), SELV (EN 60950-1)
- Overvoltage on Telecommunication Networks: TNV-1 circuit
- Electrical Safety:
- SIQ Bauart: EN 60950-1, EN 62368-1
- UL/cUL recognized:
- UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
- UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395)
- CB scheme: IEC 60950-1, IEC 62368-1
- Industrial Control Equipment:
- UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
- CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
- Hazardous Location / ATEX: (For DRP048V480W1BA)
- cCSAus: CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2007
- [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +75°C (Vertical: > +50°C derating)]
- ATEX:
- EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA nC IIC
- T4 Gc, Ta= -25°C to +75°C (Vertical: > +50°C derating)]
- Certificate No. EPS 12 ATEX 1 491 X
- CE: In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
For DRP048V480W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
- Galvanic Isolation:
- Input to Output 4.0KVac
- Input to Ground 1.5KVac
- Output to Ground 1.5KVac
*Output must be earthed in the final unit in order to comply with PELV requirements according to standard EN 60204-1
EMC
- Emissions (CE & RE):
- Generic Standards: CISPR 32, EN 55032, CISPR 11,
- EN 55011, FCC Title 47: Class B
- Component Power Supply for General Use: EN 61204-3
- Immunity: Generic Standards: EN 55024, EN 61000-6-2
- Electrostatic Discharge IEC 61000-4-2:
- Level 4 Criteria A1)
- Air Discharge: 15kV
- Contact Discharge: 8kV
- Radiated Field: IEC 61000-4-3:
- Level 3 Criteria A1)
- 80MHz-1GHz, 10V/M, 80% modulation (1kHz)
- Electrical Fast Transient / Burst: IEC 61000-4-4:
- Surge: IEC 61000-4-5:
- Level 3 Criteria A1)
- Common Mode3) : 2kV
- Differential Mode4): 1kV
- Conducted: IEC 61000-4-6:
- Level 3 Criteria A1)
- 150kHz-80MHz, 10Vrms
- Power Frequency Magnetic Fields: IEC 61000-4-8
- Voltage Dips and Interruptions: IEC 61000-4-11
- 0% of 100Vac, 20ms   Criteria A1)
- 40% of 100Vac, 200ms Criteria B2)
- 70% of 100Vac, 500ms Criteria B2)
- 0% of 100Vac, 5000ms Criteria B2)
- 0% of 240Vac, 20ms   Criteria A1)
- 40% of 240Vac, 200ms Criteria A1)
- 70% of 240Vac, 500ms Criteria A1)
- 0% of 240Vac, 5000ms  Criteria B2)
Â
- Low Energy Pulse Test: (Ring Wave): IEC 61000-4-12
- Level 3 Criteria A1)
- Common Mode3): 2kV
- Differential Mode4): 1Kv
- Harmonic Current Emission: IEC/EN 61000-3-2, Class A
- Voltage Fluctuation and Flicker: IEC/EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Asymmetrical: Common mode (Line to earth)
4) Symmetrical: Differential mode (Line to line)