Ideal for High-density power protection demand, Logix II RT NETPACK series provides Rack/Tower form factor to fit diverse environments.
Despite its compact footprint, this UPS incorporates internal battery packs which can be accessed via the front panel for maintenance checks and replacement without removing the UPS from its rack mounting.
The LCD display panel can be easily shifted to suit the installation format, vertically stand or flatly rack mount. Besides,
IT personnel can manage equipment well from learning remaining backup time information via LCD display.
Delivered with intergrated PDU & Manual Bypass and a NEXT UPS Systems SNMP/WEB Card, the UPS is ready to use.
Features
True double-conversion
Output power factor 0.9
Pure sine wave output
User-friendly and easy-shift LCD display
Rack/Tower design
Compact Design
Fan Speed Control
ECO and advanced ECO mode for energy saving
Output voltage regulation < 1%
Higher output crest radio perfect for generator and compressor
Programmable power management outlets
PDU
Emergency power off function (EPO)
Hot swappable battery design
Battery extensions available for Long runtimes
SNMP/WEB Interface included
Specifications
TYPE: Online UPS
POWER CAPACITY: 1000VA / 900W
OUTPUT POWER FACTOR: 0.90
INPUT
Input Voltage Range: 120-276 VAC Depends on Load Level
Frequency Range: 45Hz - 55Hz or 54Hz - 66Hz
Frequency (Synchronized Range): 45Hz - 55Hz or 54Hz - 66Hz
Max THDi: <5%
Input PF: ? 0.99 at full load
OUTPUT
Nominal Output Voltage: 208/220/230/240 VAC
Pure Sine Wave: Yes
THDv: ?2% Full Linear Load; ?5% Non-Linear Load
Voltage Regulation (Bat. Mod.): ±1%
Frequency (Battery Mode): ±0,2Hz
TECHNICAL DETAILS
Load Crest Ratio: 03:01
Transfer Time [AC to Battery]: 0 ms
Transfer Time [Inverter to Bypass]: 0 ms
Transfer Time [Inverter to ECO]: 1 ms
Transfer Time [ECO to Inverter]: 10 ms
Bypass: Before UPS Power-on: Default “No” Change to “Yes” via display panel /
Overload und UPS Failure: Automatically transfer to bypass / By Setting: Voltage Rang: 120-276V ± 3%